The only time adding additional fluorescent dye is required is after flushing the A/C system.
Verifying some passive leaks may require using GE-50078 Leak Detector or a SAE J2913 leak
detector, even though the refrigerant system contains fluorescent dye.
Fluorescent Leak Detection
Fluorescent dye will assist in locating any leaks in the A/C system.
Condensation on the evaporator core or the refrigerant lines may wash the compressor oil
and fluorescent dye away from the actual leak. Condensation may also carry dye through
the Heating Ventilation and Air Conditioning (HVAC) module drain.
Leaks in the A/C system will be indicated in a light green or yellow color when using the leak
detection lamp.
Use the leak detection lamp in the following areas:
– All fittings or connections that use seal washers or O-rings
– All of the A/C components
– The A/C compressor shaft seal
– The A/C hoses and pressure switches
– The HVAC module drain tube, if the evaporator core is suspected of leaking
– The service port sealing caps
– The sealing cap is the primary seal for the service ports
Follow the instructions supplied with GE-42220 Leak Detection Lamp.
To prevent false diagnosis in the future, thoroughly clean the residual dye from any area
where leaks were found. Use a rag and the approved GE-43872 Dye Cleaner.
Fluorescent Dye Injection